Assessment of Residential District Cooling System Based on Seasonal Consumption Data
摘要
Residential District Cooling Systems (DCS) are crucial for maintaining thermal comfort in urban areas, making it imperative to understand occupant cooling behavior as it significantly influences DCS operation. While several studies have investigated cooling behavior within small user groups through on-site measurements or surveys, these often fall short in representing the broader population. In this study we considered 387 homes in Hyderabad, which has a DCS connection for chilled water supply. Operational data spanning three months across different seasons were meticulously selected to assess the residents’ behavior for the cooling demand. In order to better facilitate the operation of the residential DCS, user load profile and system performance were analyzed using real world data for different seasons in the year. Our findings revealed notable disparities in DCS electrical consumption, with summer usage being 1.9 times higher than the monsoon period and 2.7 times higher than the winter period. Furthermore, a strong positive correlation emerged between outdoor temperature and thermal energy usage by the residents. On average, the daily thermal consumption per residence during winter, summer and monsoon is 3.3 kWhth, 35.1 kWhth and 10.4 kWhth respectively. Interestingly, the probability of a residence using AC during the day for the winter, summer and monsoon seasons are 0.07, 0.41 and 0.18 respectively.