Multi-level optimal energy management strategy for a grid tied microgrid considering uncertainty in weather conditions and load

  • H. E. Keshta,
  • E. G. Hassaballah,
  • A. A. Ali,
  • K. M. Abdel-Latif

摘要

Microgrids require efficient energy management systems to optimize the operation of microgrid sources and achieve economic efficiency. Bi-level energy management model is proposed in this paper to minimize the operational cost of a grid-tied microgrid under load variations and uncertainties in renewable sources while satisfying the various technical constraints. The first level is day ahead scheduling of generation units based on day ahead forecasting of renewable energy sources and load demand. In this paper, a recent meta-heuristic algorithm called Coronavirus Herd Immunity Optimizer (CHIO) is used to solve the problem of day-ahead scheduling of batteries, which is a complex constrained non-linear optimization problem, while the Lagrange multiplier method is used to determine the set-point of the Diesel Generator (DG). The second level of the proposed EMS is rescheduling and updating the set-points of sources in real-time according to the actual solar irradiance, wind speed, load, and grid tariff. In this paper, a novel real-time strategy is proposed to keep the economic operation during real-time under uncertainties. The obtained results show that the CHIO-based bi-level EMS demonstrates an optimal economic operation for a grid-connected microgrid in real-time when there are uncertainties in weather, utility tariffs, and load forecasts.