Experimental Investigation of Water-Based Fire Suppression Systems on External Façade Fires

  • Christoph Meraner,
  • Ellen S. Skilbred,
  • Kemal S. Arsava

摘要

The use of external fire suppression systems can reduce the risk of fire spreading between buildings. This study investigated the effectiveness and efficiency of different externally placed water-based fire suppression systems on façade fire safety. A series of large-scale experiments comprising an SP Fire 105 setup equipped with sprinklers and high-pressure water mist nozzles have been performed. A combustible façade, consisting of 2.5 cm thick oriented strand board (OSB) plates, was installed to provide challenging conditions and allow a visual assessment of the post-fire damage. The temperature profile on the façade surface was measured with 34 thermocouples, while five heat flux gauges and two fast-response plate thermocouples were used to measure the heat flux on the façade surface and emitted to the ambient. The sprinklers and the high-pressure water mist system effectively suppressed the upwards flame migration and reduced the heat flux toward adjacent buildings. It was observed that the sprinklers acted as a water curtain and kept the façade wet during the fire, promoting minor damage (the burnt area is less than 1% of the total area). The temperature and heat flux measurements demonstrated that the sprinkler system was the most effective suppression system. However, the high-pressure water mist systems achieved similar effectiveness but a much higher efficiency concerning water consumption. The sprinkler nozzles used four times as much water as the high-pressure water mist nozzles.